beautypg.com

Rockwell Automation 592- E300 Overload Relay User Manual User Manual

Page 340

background image

340

Rockwell Automation Publication 193-UM015B-EN-P - November 2013

Appendix B Parameter List

Analog

Monitoring

(Continued)

126

AnalogMod4Status

Analog Expansion Module 4
Status

UINT

2

1

Bit0= InCh00OpenCrcuit
Bit1= InCh00OverRange
Bit2= InCh00UnderRange
Bit3= InCh01OpenCrcuit
Bit4= InCh01OverRange
Bit5= InCh01UnderRange
Bit6= InCh02OpenCrcuit
Bit7= InCh02OverRange
Bit8= InCh02UnderRange
Bit9= OutOpenCircuit
Bit10= OutHoldLastSt
Bit11= OutOverRange
Bit12= OutUnderRange
Bit 13=Module Configured
Bit 14=Module Warning
Bit 15=Module Faulted

0

Trip/Warn
History

127

TripHistory0

Last trip to occur

UINT

2

1

See Trip History Codes

0

128

TripHistory1

Second last trip to occur

UINT

2

1

See Trip History Codes

0

129

TripHistory2

Third last trip to occur

UINT

2

1

See Trip History Codes

0

130

TripHistory3

Fourth last trip to occur

UINT

2

1

See Trip History Codes

0

131

TripHistory4

Fifth last trip to occur

UINT

2

1

See Trip History Codes

0

132

Reserved

133

WarningHistory0

Last warning to occur.

UINT

2

1

See Warning History Codes

0

134

WarningHistory1

Second last warning to occur.

UINT

2

1

See Warning History Codes

0

135

WarningHistory2

Third last warning to occur.

UINT

2

1

See Warning History Codes

0

136

WarningHistory3

Fourth last warning to occur.

UINT

2

1

See Warning History Codes

0

137

WarningHistory4

Fifth last warning to occur.

UINT

2

1

See Warning History Codes

0

138

Reserved

139

TripHistoryMaskI

Trip History Mask for Current
Based Trips

UINT

2

1

Bit0= OverloadTrip
Bit1= PhaseLossTrip
Bit2= GroundFaultTrip
Bit3= StallTrip
Bit4= JamTrip
Bit5= UnderloadTrip
Bit6= CurrentImbalTrip
Bit7= L1UnderCurrTrip
Bit8= L2UnderCurrTrip
Bit9= L3UnderCurrTrip
Bit10= L1OverCurrenTrip
Bit11= L2OverCurrenTrip
Bit12= L3OverCurrenTrip
Bit13= L1LineLossTrip
Bit14= L2LineLossTrip
Bit15= L3LineLossTrip

0xFFFF

140

TripHistoryMaskV

Trip History Mask for Voltage
Based Trips

UINT

2

1

Bit0= UnderVoltageTrip
Bit1= OvervoltageTrip
Bit2= VoltageUnbalTrip
Bit3= PhaseRotationTrp
Bit4= UnderFreqTrip
Bit5= OverFreqTrip

0x3F

Group

Param

No.

Parameter Name

Description

Type

Data Size

(bytes)

Scale

Factor

Min

Max

Default Units

This manual is related to the following products: