Chapter 4, Operating modes, Introduction – Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 75: Overload (network), Introduction overload (network), Operating, Desc, Chapter

Rockwell Automation Publication 193-UM015B-EN-P - June 2014
75
Chapter
4
Operating Modes
Introduction
The E300™ Electronic Overload Relay supports up to 54 Operating Modes which
consist of configuration rules and logic to control typical full voltage motor
starters including:
•
Overload
•
Non-Reversing Starter
•
Reversing Starter
•
Wye/Delta (Star/Delta) Starter
•
Two Speed Starter
•
Monitoring Device
This chapter explains the configuration rules, logic, and control wiring required
for the available Operating Modes (Parameter 195). Failure to follow the
configuration rules will cause the E300 Electronic Overload Relay to go into
Invalid Configuration Mode and trip the E300 Electronic Overload Relay on a
configuration trip.
Overload (Network)
The E300 Electronic Overload Relay’s default Operating Mode (Parameter 195)
is Overload (Network) in which the E300 Electronic Overload Relay operates as
a traditional overload relay with one output relay assigned as a normally closed
Trip Relay. Users can use network commands to control the remaining output
relays that are assigned as Normal output relays.
Rules
1.
One output relay must be assigned as a Trip Relay. Set any of the Output
Ptxx Assignments (Parameters 202-204) to Trip Relay.
2.
Overload Trip must be enabled in TripEnableI (Parameter 183).
Wiring Diagram
The E300 Electronic Overload Relay is wired as a traditional overload relay with
one of the output relays configured as a normally closed Trip Relay. The example
below is a wiring diagram of a Non-Reversing Starter. Relay 0 is configured as a
Trip Relay, and Relay 1 is configured as a normally open Normal Relay which
receives commands from an automation controller to energize the contactor coil.