Protective Trip and Warning Functions Chapter 5

Table 147 - Power Warning Status (Parameter 12)

Real Power (kW) Protection

The E300 Electronic Overload Relay has the capability to protect against real
power (kW) for specific applications that require the monitoring of both voltage
and current. The user can protect or issue a warning in the event that the real
power (kW) consumption of an electric motor is either too high or too low.

Under kW Inhibit Time

Under kW Inhibit Time (Parameter 378) allows the installer to inhibit an under
real power (kW) trip and warning from occurring during the motor starting
sequence. It is adjustable from 0…250 seconds.

Table 148 - Under kW Inhibit Time (Parameter 378)

Over kW Inhibit Time

Over kW Inhibit Time (Parameter 382) allows the installer to inhibit an over real
power (kW) trip and warning from occurring during the motor starting
sequence. It is adjustable from 0…250 seconds.

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Function

X

Under kW Warning

X

Over kW Warning

X

Under kVAR Consumed Warning

X

Over kVAR Consumed Warning

X

Under kVAR Generated Warning

X

Over kVAR Generated Warning

X

Under kVA Warning

X

Over kVA Warning

X

Under PF Lagging Warning

X

Over PF Lagging Warning

X

Under PF Leading Warning

X

Over PF Leading Warning

Reserved

Reserved

Reserved

Reserved

Default Value

10

Minimum Value

0

Maximum Value

250

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

1

Units

Sec