Chapter 5 Protective Trip and Warning Functions

Table 151 - UnderkW Trip Level (Parameter 380)

Under kW Warning

The E300 Electronic Overload Relay will indicate an Under kW warning if:

No warning currently exists

Under kW Warning is enabled

Current is present

Voltage is present

Under kW Inhibit Time has expired

The total real power (kW) is equal to or less than the Under kW Warning
Level

When the Under kW Warning conditions are satisfied, the:

TRIP/WARN LED will flash a yellow 2-long / 1-short blink pattern

Bit 0 in Power Warning Status (Parameter 12) will set to 1

Bit 1 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Warning Alarm will close

Under kW Warn Level

Under kW Warn Level (Parameter 381) allows the user to define the real power
(kW) at which the E300 Electronic Overload Relay will indicate a warning. It is
user-adjustable from 0…2,000,000 kW.

Default Value

0.000

Minimum Value

0.000

Maximum Value

2,000,000.000

Parameter Type

DINT

Size (Bytes)

4

Scaling Factor

1000

Units

kW

IMPORTANT

The Under kW Inhibit Time starts after a phase voltage transitions from 0V to
20V L-L and a phase of load current transitions from 0A to 30% of the device’s
minimum FLA setting. The E300 Electronic Overload Relay does not begin
monitoring for an under real power (kW) condition until the Under kW Inhibit
Time expires.