Rockwell Automation Publication 193-UM015B-EN-P - June 2014

147

Protective Trip and Warning Functions Chapter 5

Over Frequency Inhibit Time

Over Frequency Inhibit Time (Parameter 373) allows the installer to inhibit an
over frequency trip and warning from occurring during the motor starting
sequence. It is adjustable from 0…250 seconds.

Table 136 - Over Frequency Inhibit Time (Parameter 373)

Under Frequency Trip

The E300 Electronic Overload Relay will trip with an Under Frequency
indication if:

No trip currently exists

Under Frequency Trip is enabled

Voltage is present

Under Frequency Inhibit Time has expired

The voltage frequency is less than the Under Frequency Trip Level for a
time period greater than the Under Frequency Trip Delay.

If the E300 Electronic Overload Relay trips on an under frequency, the:

TRIP/WARN LED status indicator will flash a red 1-long / 5-short blink
pattern

Bit 4 in Voltage Trip Status (Parameter 5) will set to 1

Bit 0 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Trip Relay will open

Any relay outputs configured as a Control Relay will open

Any relay outputs configured as a Trip Alarm will close

Any relay outputs configured as a Normal Relay will be placed in their
Protection Fault state (if so programmed)

Default Value

10

Minimum Value

0

Maximum Value

250

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

1

Units

Sec