Rockwell Automation Publication 193-UM015B-EN-P - June 2014

119

Protective Trip and Warning Functions Chapter 5

Table 104 - L1 Over Current Trip Delay (Parameter 276)

L1 Over Current Trip Level

L1 Over Current Trip Level (Parameter 277) allows the installer to define the
current at which the E300 Electronic Overload Relay will trip on a L1 Over
Current. It is user-adjustable from 10…100% of the FLA Setting (Parameter
171).

Table 105 - L1 Over Current Trip Level (Parameter 277)

L1 Over Current Warning

The E300 Electronic Overload Relay will indicate an L1 Over Current warning
if:

No warning currently exists

1 Over Current Warning is enabled

Current is present

The Over Current Inhibit Timer has expired

1 Percent FLA (Parameter 47) is greater than the L1 Over Current
Warning Level

When the L1 Over Current Warning conditions are satisfied, the:

TRIP/WARN LED will flash a yellow 11-short blink pattern

Bit 10 in Current Warning Status (Parameter 10) will set to 1

Bit 1 in Device Status 0 (Parameter 20) will set to 1

Default Value

1.0

Minimum Value

0.1

Maximum Value

25.0

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

10

Units

Sec

Default Value

100

Minimum Value

10

Maximum Value

100

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

1

Units

%FLA

IMPORTANT

The Over Current Inhibit Timer starts after the maximum phase of load current
transitions from 0A to 30% of the device’s minimum FLA setting. The E300
Electronic Overload Relay does not begin monitoring for an over current
condition until the Over Current Inhibit Time expires.