Test mode, Invalid configuration mode, Test mode invalid configuration mode – Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 53
![background image](/manuals/577641/53/background.png)
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
53
System Operation and Configuration Chapter 3
Table 20 - Run Mode Bit Function Detail — Device Status 0 (Parameter 20)
Test Mode
Test Mode is used by installers of motor control centers who are testing and
commissioning motor starters with an automation system. A digital input of the
E300 Electronic Overload Relay is assigned to monitor the motor control center
enclosure’s Test Position. The Input Assignments (Parameters 196-201) are
described later in this chapter.
Users commissioning motor starters in an automation system can put their motor
control center enclosure into the Test Position to activate Test Mode and verify
that the digital inputs and relay outputs of the E300 Electronic Overload Relay
are operating properly with the motor starter without energizing power to the
motor. If the E300
Electronic Overload Relay senses current or voltage in Test
Mode, the E300 Electronic Overload Relay will generate a Test Mode Trip.
Invalid Configuration Mode
Invalid Configuration Mode is an active mode for the E300 Electronic Overload
Relay in which the E300 is in a tripped state due to invalid configuration data.
Invalid Configuration Parameter (Parameter 38) indicates the parameter number
that is causing the fault. Invalid Configuration Cause (Parameter 39) identifies
the reason for Invalid Configuration Mode.
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Function
X
Trip Present
X
Warning Present
X
Invalid Configuration
X
Current Present
X
GFCurrent Present
X
Voltage Present
X
Emergency Start Enabled
X
DeviceLogix Enabled
X
Feedback Timeout Enabled
X
Operator Station Present
X
Voltage Sensing Present
X
Intern Ground Fault Sensing Present
X
Extern Ground Fault Sensing Present
X
PTC Sensing
X
Ready
Reserved