Chapter 5 Protective Trip and Warning Functions

Under Power Factor Leading Trip

The E300 Electronic Overload Relay will trip with an Under Power Factor
Leading indication if:

No trip currently exists

Under Power Factor Leading Trip is enabled

Current is present

Voltage is present

Under Power Factor Leading Inhibit Time has expired

The total power factor leading is less than the Under Power Factor Leading
Trip Level for a time period greater than the Under Power Factor Leading
Trip Delay.

If the E300 Electronic Overload Relay trips on an under power factor leading,
the:

TRIP/WARN LED status indicator will flash a red 2-long / 11-short
blink pattern

Bit 10 in Power Trip Status (Parameter 6) will set to 1

Bit 0 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Trip Relay will open

Any relay outputs configured as a Control Relay will open

Any relay outputs configured as a Trip Alarm will close

Any relay outputs configured as a Normal Relay will be placed in their
Protection Fault state (if so programmed)

IMPORTANT

The Over Power Factor Lagging Warning function does not include a time delay
feature. Once the Over Power Factor Lagging Inhibit Time has expired, the Over
Power Factor Lagging Warning indication is instantaneous.