Appendix C EtherNet/IP Information

Table 369 -

Instance 2 — Basic Overload Output Assembly from ODVA Profile

Table 370 - Instance 2 Attributes

Instance 50

The following table summarizes Attribute 3 Format:

Table 371 - Instance 50 — Basic Overload Input Assembly from ODVA Overload Profile

Table 372 - Instance 50 Attributes

Instance 120 - Configuration Assembly Revision 2

The following table shows Attribute 3 Format and Attribute 2 Member List for
revision 2 of the assembly.

Table 373 - Instance 120 — Configuration Assembly

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Fault Reset

Attribute ID Access Rule Member Index Name

Data Type

Value

1

Get

Number of Members in Member List

UINT

2

2

Get

Member List

Array of STRUCT

0

Member Data Description

UINT

2

Member Path Size

UINT

0

Member Path

Packed EPATH

1

Member Data Description

UINT

1

Member Path Size

UINT

12

Member Path

Packed EPATH

6BH & “Fault Reset”

3

Set

Data

UINT

See data format above

4

Get

Size

UINT

1

100

Get

Name

SHORT_STRING

“Trip Reset Cmd”

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Tripped

Attribute ID Access Rule Member Index

Name

Data Type

Value

1

Get

Number of Members in Member List UINT

1

2

Get

Member List

Array of STRUCT

0

Member Data Description

UINT

1

Member Path Size

UINT

8

Member Path

Packed EPATH

67H & “Tripped”

3

Get

Data

UINT

See data format above

4

Get

Size

UINT

1

100

Get

Name

SHORT_STRING

“Trip Status”

INT

DINT 15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Size (bits) Param

0

0

ConfigAssyRev = 2

16

1100

1

SetOperatingMode

8

195

Reserved

8

1102