beautypg.com

Rockwell Automation 592- E300 Overload Relay User Manual User Manual

Page 143

background image

Rockwell Automation Publication 193-UM015B-EN-P - June 2014

143

Protective Trip and Warning Functions Chapter 5

Table 130 - Voltage Imbalance Trip Delay (Parameter 366)

Voltage Imbalance Trip Level

Voltage Imbalance Trip Level (Parameter 367) allows the installer to define the
percentage at which the E300 Electronic Overload Relay will trip on a voltage
imbalance. It is user-adjustable from 10…100%.

Table 131 - Voltage Imbalance Trip Level (Parameter 367)

Voltage Imbalance Warning

The E300 Electronic Overload Relay will indicate a voltage imbalance warning
if:

No warning currently exists

Voltage Imbalance Warning is enabled

Voltage is present

Voltage Imbalance Inhibit Time has expired

The Voltage Imbalance (Parameter 61) is greater than the Voltage
Imbalance Warning Level

When the Voltage Imbalance Warning conditions are satisfied, the:

TRIP/WARN LED will flash a yellow red 1-long / 3-short blink pattern

Bit 2 in Voltage Warning Status (Parameter 11) will set to 1

Bit 1 in Device Status 0 (Parameter 20) will set to 1

Default Value

1.0

Minimum Value

0.1

Maximum Value

25.0

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

10

Units

Sec

Default Value

15

Minimum Value

10

Maximum Value

100

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

1

Units

%

IMPORTANT

The Voltage Imbalance Inhibit Timer starts after a phase voltage transitions
from 0V to 20V L-L. The E300 Electronic Overload Relay does not begin
monitoring for a voltage imbalance condition until the Voltage Imbalance
Inhibit Time expires.

This manual is related to the following products: