Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 351
Rockwell Automation Publication 193-UM015B-EN-P - November 2013
351
Parameter List Appendix B
Current Setup
239
PLInhibitTime
Phase Loss Inhibit Time
USINT
1
1
0
250
0
Sec
240
PLTripDelay
Phase Loss Trip Delay
USINT
1
10
1
250
10
Sec
241
GroundFaultType
Select Ground Fault Type
USINT
1
1
0= Disabled
1= Internal1to5Amps
2= ExtPt02toPt1Amps
3= ExtPt1toPt5Amps
4= ExtPt5to1Amps
5= External1to5Amps
0
242
GFInhibitTime
Ground Fault Inhibit Time
USINT
1
1
0
250
10
Sec
243
GFTripDelay
Ground Fault Trip Delay
USINT
1
10
0
250
5
Sec
244
GFTripLevel
Ground Fault Trip Level
UINT
2
100
2
500
200
Amps
245
GFWarningDelay
Ground Fault Warning Delay
USINT
1
10
0
250
0
Sec
246
GFWarningLevel
Ground Fault Warning Level
UINT
2
100
2
500
200
Amps
247
GFFilter
Filter GF current from %TCU
calculation
BOOL
1
1
0=Disable
1=Enable
0
248
GFMaxInhibit
Trip is inhibited when GF exceeds
max value
BOOL
1
1
0=Disable
1=Enable
0
249
StallEnabledTime
Stall Monitor and Trip Delay
USINT
1
1
0
250
10
Sec
250
StallTripLevel
Stall Trip Level
UINT
2
10
100
600
600
%FLA
251
JamInhibitTime
Jam Detect Inhibit Time
USINT
1
1
0
250
10
Sec
252
JamTripDelay
Jam Detect Trip Delay
USINT
1
10
1
250
50
Sec
253
JamTripLevel
Jam Detect Trip Level
UINT
2
1
50
600
250
%FLA
254
JamWarningLevel
Jam Detect Warning Level
UINT
2
1
50
600
150
%FLA
255
ULInhibitTime
Underload Inhibit Time
USINT
1
1
0
250
10
Sec
256
ULTripDelay
Underload Trip Delay
USINT
1
10
1
250
50
Sec
257
ULTripLevel
Underload Trip Level
USINT
1
1
10
100
50
%FLA
258
ULWarningLevel
Underload Warning Level
USINT
1
1
10
100
70
%FLA
259
CIInhibitTime
Current Imbalance Inhibit Time
USINT
1
1
0
250
10
Sec
260
CITripDelay
Current Imbalance Trip Delay
USINT
1
10
1
250
50
Sec
261
CITripLevel
Current Imbalance Trip Level
USINT
1
1
10
100
35
%
262
CIWarningLevel
Current Imbalance Warning Level USINT
1
1
10
100
20
%
263
CTPrimary
Current Transformer Primary
Ratio
UINT
2
1
1
65535
5
264
CTSecondary
Current Transformer Secondary
Ratio
UINT
2
1
1
65535
5
265
UCInhibit Time
Under Current Inhibit Time
USINT
1
1
0
250
10
Sec
266
L1UCTripDelay
L1 Under Current Trip Delay
USINT
1
10
0
250
10
Sec
267
L1UCTripLevel
L1 Under Current Trip Level
USINT
1
1
10
100
35
%
268
L1UCWarningLevel
L1 Under Current Warning Level
USINT
1
1
10
100
40
%
269
L2UCTripDelay
L2 Under Current Trip Delay
USINT
1
10
0
250
10
Sec
270
L2UCTripLevel
L2 Under Current Trip Level
USINT
1
1
10
100
35
%
271
L2UCWarningLevel
L2 Under Current Warning Level
USINT
1
1
10
100
40
%
272
L3UCTripDelay
L3 Under Current Trip Delay
USINT
1
10
0
250
10
Sec
273
L3UCTripLevel
L3 Under Current Trip Level
USINT
1
1
10
100
35
%
274
L3UCWarningLevel
L3 Under Current Warning Level
USINT
1
1
10
100
40
%
275
OCInhibitTime
Over Current Inhibit Time
USINT
1
1
0
250
10
Sec
276
L1OCTripDelay
L1 Over Current Trip Delay
USINT
1
10
0
250
10
Sec
277
L1OCTripLevel
L1 Over Current Trip Level
USINT
1
1
10
200
100
%
278
L1OCWarningLevel
L1 Over Current Warning Level
USINT
1
1
10
200
90
%
Group
Param
No.
Parameter Name
Description
Type
Data Size
(bytes)
Scale
Factor
Min
Max
Default Units