Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Appendix A Specifications
Low Voltage Directive
The E300 Electronic Overload Relay expansion digital modules are tested to
comply with EN60947-5-1 Low-voltage switchgear and controlgear Part 5-1:
Control circuit devices and switching elements.
Utilization Category
AC-15
Resistive Load Rating (p.f. = 1.0)
5 A, 250V AC
5 A, 30V DC
Inductive Load Rating (p.f. = 0.4)
(L/R = 7 ms)
2 A, 250V AC
2 A, 30V DC
Short Circuit Current Rating
1,000 A
Recommended Control Circuit Fuse
KTK-R-6
(6 A, 600 V)
Rated Number of Operations
Relay 0, Relay 1, and Relay 2:
W/100-C09…100-C43
W/100-C60…100-C85
W/NEMA Size 0…2
W/NEMA Size 3
5,000,000
2,500,000
1,000,000
300,000
Table 346 - Input Ratings (Control Module and Expansion Digital Module)
Terminals
Input 0:
Input 1:
Input 2:
Input 3:
Input 4:
Input 5:
IN0
IN1
IN2
IN3
IN4
IN5
Supply Voltage
24V DC
120V AC
240V AC
Type of Inputs
Current Sinking
On-State Voltage
11V DC
74V AC
159V AC
On-State Current (turn-on)
2 mA
5 mA
5 mA
Off-State Voltage
5V DC
20V AC
40V AC
Off-State Current
1.5 mA
2.5 mA
2.5 mA
Transition Voltage
5...11V DC
20…74V AC
40…159V AC
Transition Current
1.5...2.0 mA
2.5…5 mA
2.5…5 mA
Table 347 - Thermistor/PTC Input Ratings (PTC only)
Terminals
IT1, IT2
Type of Control Unit
Mark A
Maximum Number of Sensors
6
Maximum Cold Resistance of PTC Sensor Chain
1500
Trip Resistance
3400
± 150
Reset Resistance
1600
± 100
Short-circuit Trip Resistance
25
± 10
Maximum Voltage @ PTC Terminals (R
PTC
= 4 k
)
7.5V DC
Maximum Voltage @ PTC Terminals (R
PTC
=open)
30V DC
Response Time
800 ms
Table 345 - Output Relay Ratings (Control Module and Expansion Digital Module)