Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 267
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
267
Metering and Diagnostics Chapter 7
26
Sensing Module output enable open
27
Sensing Module missing interrupts
28
Sensing Module not calibrated
29
Sensing Module frame type failure
30
Sensing Module flash configuration failure
31
Sensing Module detected an overrun error
32
Sensing Module is not responding
33
Total Real Power(kW)is below trip level
34
Total Real Power(kW)has exceeded trip level
35
Under Total Reactive Power Consumed (+kVAR) condition detected
36
Over Total Reactive Power Consumed (+kVAR) condition detected
37
Under Total Reactive Power Generated (-kVAR) condition detected
38
Over Total Reactive Power Generated (-kVAR) condition detected
39
Total Apparent Power (VA or kVA or MVA) is below trip level
40
Total Apparent Power (VA or kVA or MVA) exceeded trip level
41
Under Total Power Factor Lagging (-PF) condition detected
42
Over Total Power Factor Lagging (-PF) condition detected
43
Under Total Power Factor Leading (+PF) condition detected
44
Over Total Power Factor Leading (+PF) condition detected
49
Test trip caused by holding the Test/Reset button for 2 seconds
50
PTC input indicates that the motor stator windings overheated
51
DeviceLogix defined trip was generated
52
The Stop button the Operator Station was pressed
53
Remote trip command detected
54
Maximum starts per hour exceeded
55
Hardware configuration fault. Check for shorts on input terminal
56
Invalid parameter config. See parameters 38-39 for details
58
DeviceLogix Feedback Timeout Trip was detected
59
Control Module CAN0 initialization failure
60
Control Module CAN0 bus failure
61
Control Module CAN1 initialization failure
62
Control Module CAN1 bus failure
63
Control Module ADC0 failure
64
Control Module detected too many CRC errors
65
Input Channel 00 on Analog Module 1 exceeded its Trip Level
66
Input Channel 01 on Analog Module 1 exceeded its Trip Level
67
Input Channel 02 on Analog Module 1 exceeded its Trip Level
68
Input Channel 00 on Analog Module 2 exceeded its Trip Level
69
Input Channel 01 on Analog Module 2 exceeded its Trip Level
70
Input Channel 02 on Analog Module 2 exceeded its Trip Level
71
Input Channel 00 on Analog Module 3 exceeded its Trip Level
72
Input Channel 01 on Analog Module 3 exceeded its Trip Level
73
Input Channel 02 on Analog Module 3 exceeded its Trip Level
Trip History Code
Description