Protective Trip and Warning Functions Chapter 5

Table 124 - Under Voltage Trip Level (Parameter 357)

Under Voltage Warning

The E300 Electronic Overload Relay will indicate an Under Voltage warning if:

No warning currently exists

Under Voltage Warning is enabled

Voltage is present

Under Voltage

Inhibit Time has expired

The minimum phase voltage is equal to or less than the Under Voltage
Warning Level

When the Under Voltage Warning conditions are satisfied, the:

TRIP/WARN LED will flash a yellow 1-long / 1-short blink pattern

Bit 0 in Voltage Warning Status (Parameter 11) will set to 1

Bit 1 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Warning Alarm will close

Under Voltage Warn Level

Under Voltage Warn Level (Parameter 358) allows the user to define the voltage
at which the E300 Electronic Overload Relay will indicate a warning. It is user-
adjustable from 0…6553.5 volts.

Table 125 - Under Voltage Warn Level

Default Value

100.0

Minimum Value

0.0

Maximum Value

6553.5

Parameter Type

UINT

Size (Bytes)

2

Scaling Factor

10

Units

Volts

IMPORTANT

The Under Voltage Inhibit Time starts after a phase voltage transitions from 0V
to 20V L-L. The E300 Electronic Overload Relay does not begin monitoring for
an under voltage condition until the Under Voltage Inhibit Time expires.

Default Value

400.0

Minimum Value

0.0

Maximum Value

6553.5

Parameter Type

UINT

Size (Bytes)

2

Scaling Factor

10

Units

Volts