Appendix B Parameter List
Analog3 Setup
(continued)
516
InAMod3C1WarnLvl
Level (in selected Units) where
Analog Input generates a
warning
UINT
2
1
0
65535
0
517
InAnMod3Ch02Type
Assignment for Analog Module 3
Input Channel 02 function
USINT
1
1
0= Disabled
1= 4To20mA
2= 0To20mA
3= 0To10Volts
4= 1To5Volts
5= 0To5Volts
6= 100Pt385
7= 200Pt385
8= 500Pt385
9= 1000Pt385
10=100Pt3916
11= 200Pt3916
12= 500Pt3916
13= 1000Pt3916
14= 10Cu426
15= 120Ni618
16= 120Ni672
17= 604NiFe518
18= 150ohm
19= 1000ohm
20 = 3000ohm
21= 6000ohm
0
518
InAMod3Ch2Format
Assignment for Analog Module 3
Input Channel 02 Data Format
USINT
1
1
0= EngUnits
1= EngUnitsTimes10
2= RawProportional
3= ScaledForPID
0
519
InAMod3C2TmpUnit
Assignment for Analog Module 3
Input Channel 02 Temperature
Units
USINT
1
1
0=DegreesC
1=DegreesF
0
520
InAMod3C2FiltFrq
Indicates Analog Module 3 Input
Channel 02 Filter Freq
USINT
1
1
0=17Hz
1=4Hz
2=62Hz
3=470Hz
0
521
InAMod3C2OpCktSt
Indicates Analog Module 3 Input
Channel 02 Open Circuit State
USINT
1
1
0=Upscale
1=Downscale
2=Zero
0
522
InAnMod3Ch2RTDEn
Enable Analog Module 3 Input
Channel 02 to function with RTD
BOOL
1
1
0=3-wire
1=2-wire
0
523
InAMod3C2TripDly
Analog Module 3 Input Channel
02 Trip Delay
USINT
1
10
0
250
10
Sec
524
InAMod3C2TripLvl
Level (in selected Units) where
Analog Input generates a trip
UINT
2
1
0
65535
0
525
InAMod3C2WarnLvl
Level (in selected Units) where
Analog Input generates a
warning
UINT
2
1
0
65535
0
526
OutAnMod3Type
Assignment for Analog Module 3
Output function
USINT
1
1
0= Disabled
1= 4To20mA
2= 0To20mA
3= 0To10Volts
4=1to5 Volts
5=0to5 Volts
0
Group
Param
No.
Parameter Name
Description
Type
Data Size
(bytes)
Scale
Factor
Min
Max
Default Units