Rockwell Automation Publication 193-UM015B-EN-P - June 2014

51

Chapter

3

System Operation and Configuration

Introduction

This chapter provides instructions for operating and configuring an E300
Electronic Overload Relay system. Settings for Device Modes, Option Match,
Security Policy, I/O Assignments, Expansion Bus Fault, Emergency Start, and an
introduction to Operating Modes are included in this chapter.

Device Modes

The E300 Electronic Overload Relay has five device modes to validate
configuration of the device and limit when a user can configure the E300
Electronic Overload Relay, perform a firmware update, and issue commands.

Administration Mode

Operation Mode

Run Mode

Test Mode

Invalid Configuration Mode

Administration Mode

Administration Mode is a maintenance mode for the E300 Electronic Overload
Relay which allows users to configure parameters, modify security policies, enable
web servers (see

page 286

to enable the EtherNet/IP web server), perform

firmware upgrades, and issue commands.

Follow these steps to enter into Administration Mode:

1.

Set the rotary dials on the E300 Communication Module to the following
values

For EtherNet/IP set the rotary dials to 0-0-0

For DeviceNet set the rotary dials to 7-7

2.

Cycle power on the E300 Electronic Overload Relay

After commissioning activities and maintenance tasks are completed, return the
E300 Electronic Overload Relay back to Operation or Run Mode by setting the
rotary dials of the E300 communication module back to its previous positions
and cycle power.