Protective Trip and Warning Functions Chapter 5

Starts Interval

Starts Interval (Parameter 206) is the time that the user must wait between starts.
This value is adjustable from 0…3600 seconds.

Table 201 - Starts Interval (Parameter 206)

Starts Available

Starts Available (Parameter 30) reports the number of starts currently available
based on the blocked start settings and the actual motor starting events.

Table 202 - Starts Available (Parameter 30)

Time to Start

Time to Start (Parameter 31) reports the amount of the time remaining until a
new start can be issued. If the Time to Start time has elapsed, this parameter will
report zero until the next Blocked Start trip occurs.

Table 203 - Time to Start (Parameter 31)

Default Value

600

Minimum Value

0

Maximum Value

3600

Parameter Type

UINT

Size (Bytes)

2

Scaling Factor

1

Units

Sec

Default Value

0

Minimum Value

0

Maximum Value

120

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

1

Units

Default Value

0

Minimum Value

0

Maximum Value

3600

Parameter Type

UINT

Size (Bytes)

2

Scaling Factor

1

Units

Sec