Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 364
![background image](/manuals/577641/364/background.png)
364
Rockwell Automation Publication 193-UM015B-EN-P - November 2013
Appendix B Parameter List
Analog2 Setup
(continued)
496
OutAnMod2Select
Assignment of parameter data
value to drive Analog Module 2
Output
USINT
1
1
0= AveragePctFLA
1= ScaledAvgPctFLA
2= PercentTCU
3= GFCurrent
4= CurrentUnbalance
5= AvgLLVoltage
6=VoltLLUnbalance
7= TotalkW
8= TotalkVA
9= TotalkVAR
10= TotalPF
11= UserDLXData
0
497
OutAnMod2FltActn
Analog Module 2 Output action
on comms fault
USINT
1
1
0= Zero
1= Maximum
2= Minimum
3= HoldLastState
0
Analog3 Setup
498
OutAnMod2IdlActn
Analog Module 2 Output action
on comms idle
USINT
1
1
0= Zero
1= Maximum
2= Minimum
3= HoldLastState
0
499
InAnMod3Ch00Type
Assignment for Analog Module 3
Input Channel 00 function
USINT
1
1
0= Disabled
1= 4To20mA
2= 0To20mA
3= 0To10Volts
4= 1To5Volts
5= 0To5Volts
6= 100Pt385
7= 200Pt385
8= 500Pt385
9= 1000Pt385
10=100Pt3916
11= 200Pt3916
12= 500Pt3916
13= 1000Pt3916
14= 10Cu426
15= 120Ni618
16= 120Ni672
17= 604NiFe518
18= 150ohm
19= 1000ohm
20 = 3000ohm
21= 6000ohm
0
500
InAMod3Ch0Format
Assignment for Analog Module 3
Input Channel 00 Data Format
USINT
1
1
0= EngUnits
1= EngUnitsTimes10
2= RawProportional
3= ScaledForPID
0
501
InAMod3C0TmpUnit
Assignment for Analog Module 3
Input Channel 00 Temperature
Units
USINT
1
1
0=DegreesC
1=DegreesF
0
502
InAMod3C0FiltFrq
Assignment for Analog Module 3
Input Channel 00 Filter Freq
USINT
1
1
0=17Hz
1=4Hz
2=62Hz
3=470Hz
0
Group
Param
No.
Parameter Name
Description
Type
Data Size
(bytes)
Scale
Factor
Min
Max
Default Units