beautypg.com

Hardware fault – Rockwell Automation 592- E300 Overload Relay User Manual User Manual

Page 204

background image

204

Rockwell Automation Publication 193-UM015B-EN-P - June 2014

Chapter 5 Protective Trip and Warning Functions

Table 207 - Operating Time (Parameter 28)

Hardware Fault

The E300 Electronic Overload Relay continuously monitors the status of the
Control, Sensing, and Communication Modules. The E300 Electronic Overload
Relay will issue a hardware fault trip if there is an issue with the Control, Sensing,
and Communications Modules or if one of the modules is missing or
incompatible. The Hardware Fault Trip is always enabled.

The E300 Electronic Overload Relay will trip with a hardware fault trip
indication if:

No trip currently exists

Hardware Fault Trip is enabled

An issue exists between the Control Module, Sensing Module, and/or
Communication Module

If the E300 Electronic Overload Relay trips on a hardware fault trip, the
following will occur:

The TRIP/WARN LED will flash a red 3-long / 7-short blink pattern

Bit 6 in Control Trip Status (Parameter 7) will set to 1

Bit 0 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Trip Relay will open

Any relay outputs configured as a Control Relay will open

Any relay outputs configured as a Trip Alarm will close

Any relay outputs configured as a Normal Relay will be placed in their
Protection Fault state (if so programmed)

Default Value

0

Minimum Value

0

Maximum Value

65535

Parameter Type

UINT

Size (Bytes)

2

Scaling Factor

1

Units

Hours

This manual is related to the following products: