Protective Trip and Warning Functions Chapter 5

Ground Fault Current is equal to or greater than the Ground Fault
Warning Level for a time period greater than the Ground Fault Warning
Delay.

When the ground fault warning conditions are satisfied, the:

TRIP/WARN LED status indicator will flash a yellow 3-short blink
pattern

Bit 2 in Current Warning Status (Parameter 10) will set to 1

Bit 1 of Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Warning Alarm will close

Ground Fault Warning Level

Ground Fault Warning Level (Parameter 246) allows the user to define the
ground fault current at which the E300 Electronic Overload Relay will indicate a
warning and is adjustable from 0.20…5.00 A.

Table 77 - Ground Fault Warning Level (Parameter 246)

Ground Fault Warning Delay

Ground Fault Warning Delay (Parameter 245) allows the user to define the time
period (adjustable from 0.0…25.0 s) for which a ground fault condition must be
present before a warning occurs.

Table 78 - Ground Fault Warning Delay (Parameter 245)

Ground Fault Warning Level (Parameter 246)

Default Value

2.00

Minimum Value

0.20

Maximum Value

5.00

Parameter Type

UINT

Size (Bytes)

2

Scaling Factor

100

Units

Amps

Ground Fault Warning Delay (Parameter 245)

Default Value

0.0

Minimum Value

0.0

Maximum Value

25.00

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

10

Units

Sec