Rockwell Automation Publication 193-UM015B-EN-P - June 2014

Appendix C EtherNet/IP Information

The table below lists Fault Codes, Fault Text, and Fault Help Strings.

Table 425 - Fault Codes, Fault Text, and Fault Help Strings

Fault Code

Fault Text

Help Text

0

No Fault

No Fault Conditions Detected

1

OverloadTrip

Motor current overload condition

2

PhaseLossTrip

Phase current Loss detected in one of the motor phases

3

GroundFaultTrip

Power conductor or motor winding is shorting to ground

4

StallTrip

Motor has not reached full speed by the end of Stall Enable Time

5

JamTrip

Motor current has exceed the programmed jam trip level

6

UnderloadTrip

Motor current has fallen below normal operating levels

7

Current Imbal

Phase to phase current imbalance detected

8

L1UnderCurrTrip

L1Current was below L1 Undercurrent Level longer than Trip Delay

9

L2UnderCurrTrip

L2Current was below L2 Undercurrent Level longer than Trip Delay

10

L3UnderCurrTrip

L3Current was below L3 Undercurrent Level longer than Trip Delay

11

L1OverCurrenTrip

L1 Current was over L1 Overcurrent Level longer than Trip Delay

12

L2OverCurrenTrip

L2 Current was over L2 Overcurrent Level longer than Trip Delay

13

L3OverCurrenTrip

L3 Current was over L3 Overcurrent Level longer than Trip Delay

14

L1LineLossTrip

L1 Current Lost for longer than the L1 Loss Trip Delay

15

L2LineLossTrip

L2 Current Lost for longer than the L2 Loss Trip Delay

16

L3LineLossTrip

L3 Current Lost for longer than the L3 Loss Trip Delay

17

UnderVoltageTrip

Line to Line Under-Voltage condition detected

18

OverVoltageTrip

Line to Line Over-Voltage condition detected

19

VoltageUnbalTrip

Phase to phase voltage imbalance detected

20

PhaseRotationTrp

The unit detects the supply voltage phases are rotated

21

UnderFreqTrip

Line voltage frequency is below trip level

22

OverFreqTrip

Line voltage frequency has exceeded trip level

23

Fault23

24

Fault24

25

Fault25

26

Fault26

27

Fault27

28

Fault28

29

Fault29

30

Fault30

31

Fault31

32

Fault32

33

UnderKWTrip

Total Real Power(kW)is below trip level

34

OverKWTrip

Total Real Power(kW)has exceeded trip level

35

UnderKVARConTrip

Under Total Reactive Power Consumed (+kVAR) condition detected

36

OverKVARConTrip

Over Total Reactive Power Consumed (+kVAR) condition detected

37

UnderKVARGenTrip

Under Total Reactive Power Generated (-kVAR) condition detected

38

OverKVARGenTrip

Over Total Reactive Power Generated (-kVAR) condition detected

39

UnderKVATrip

Total Apparent Power (VA or kVA or MVA) is below trip level

40

OverKVATrip

Total Apparent Power (VA or kVA or MVA) exceeded trip level

41

UnderPFLagTrip

Under Total Power Factor Lagging (-PF) condition detected

42

OverPFLagTrip

Over Total Power Factor Lagging (-PF) condition detected

43

UnderPFLeadTrip

Under Total Power Factor Leading (+PF) condition detected

44

OverPFLeadTrip

Over Total Power Factor Leading (+PF) condition detected

45

Fault45

46

Fault46