Chapter 5 Protective Trip and Warning Functions

Under Power Factor Leading Inhibit Time

Under Power Factor Leading Inhibit Time (Parameter 418) allows the installer to
inhibit an under power factor leading trip and warning from occurring during the
motor starting sequence. It is adjustable from 0…250 seconds.

Table 182 - Under Power Factor Leading Inhibit Time (Parameter 418)

Over Power Factor Leading Inhibit Time

Over Power Factor Leading Inhibit Time (Parameter 422) allows the installer to
inhibit an over power factor leading trip and warning from occurring during the
motor starting sequence. It is adjustable from 0…250 seconds.

Table 183 - Over Power Factor Leading Inhibit Time (Parameter 422)

Under Power Factor Lagging Trip

The E300 Electronic Overload Relay will trip with an Under Power Factor
Lagging indication if:

No trip currently exists

Under Power Factor Lagging Trip is enabled

Current is present

Voltage is present

Under Power Factor Lagging Inhibit Time has expired

The total power factor lagging is less than the Under Power Factor Lagging
Trip Level for a time period greater than the Under Power Factor Lagging
Trip Delay.

Default Value

10

Minimum Value

0

Maximum Value

250

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

1

Units

Sec

Default Value

10

Minimum Value

0

Maximum Value

250

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

1

Units

Sec