Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 182
182
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Chapter 5 Protective Trip and Warning Functions
Under Power Factor Leading Inhibit Time
Under Power Factor Leading Inhibit Time (Parameter 418) allows the installer to
inhibit an under power factor leading trip and warning from occurring during the
motor starting sequence. It is adjustable from 0…250 seconds.
Table 182 - Under Power Factor Leading Inhibit Time (Parameter 418)
Over Power Factor Leading Inhibit Time
Over Power Factor Leading Inhibit Time (Parameter 422) allows the installer to
inhibit an over power factor leading trip and warning from occurring during the
motor starting sequence. It is adjustable from 0…250 seconds.
Table 183 - Over Power Factor Leading Inhibit Time (Parameter 422)
Under Power Factor Lagging Trip
The E300 Electronic Overload Relay will trip with an Under Power Factor
Lagging indication if:
•
No trip currently exists
•
Under Power Factor Lagging Trip is enabled
•
Current is present
•
Voltage is present
•
Under Power Factor Lagging Inhibit Time has expired
•
The total power factor lagging is less than the Under Power Factor Lagging
Trip Level for a time period greater than the Under Power Factor Lagging
Trip Delay.
Default Value
10
Minimum Value
0
Maximum Value
250
Parameter Type
USINT
Size (Bytes)
1
Scaling Factor
1
Units
Sec
Default Value
10
Minimum Value
0
Maximum Value
250
Parameter Type
USINT
Size (Bytes)
1
Scaling Factor
1
Units
Sec