Chapter 7 Metering and Diagnostics

Table 270 - L2 Real Power (Parameter 65)

L3 Real Power

L3 Real Power (Parameter 66) reports the real power for line 3 in kW or MW
depending on the configuration value for Power Scale (Parameter 377). When
Voltage Mode (Parameter 352) is set to any

Delta base setting, L3 Real Power is

set to 0. When Single or Three Phase (Parameter 176) is set to

Single Phase, L3

Real Power is set to 0.

Table 271 - L3 Real Power (Parameter 66)

Total Real Power

Total Real Power (Parameter 67) reports the total real power of the monitored
power conductors in kW or MW depending on the configuration value for
Power Scale (Parameter 377). When Single or Three Phase (Parameter 176) is
set to

Three Phase, Total Real Power is calculated as follows:

Total Real Power = (L1 Real Power + L2 Real Power + L3 Real Power)

When Single or Three Phase (Parameter 176) is set to

Single Phase, Total Real

Power is calculated as follows:

Total Real Power = (L1 Real Power + L2 Real Power)

Default Value

0.000

Minimum Value

-2000000.000

Maximum Value

2000000.000

Parameter Type

DINT

Size (Bytes)

4

Scaling Factor

1000

Units

kW or MW

Default Value

0.000

Minimum Value

-2000000.000

Maximum Value

2000000.000

Parameter Type

DINT

Size (Bytes)

4

Scaling Factor

1000

Units

kW or MW