Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 157

Rockwell Automation Publication 193-UM015B-EN-P - June 2014
157
Protective Trip and Warning Functions Chapter 5
Under kW Trip Delay
Under kW Trip Delay (Parameter 379) allows the installer to define the time
period an under real power (kW) condition must be present before a trip occurs.
It is adjustable from 0.1…25.0 seconds.
Table 150 - Under kW Trip Delay (Parameter 379)
Under kW Trip Level
Under kW Trip Level (Parameter 380) allows the installer to define the real
power (kW) at which the E300 Electronic Overload Relay will trip on an under
real power (kW). It is user-adjustable from 0…2,000,000 kW.
IMPORTANT
The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:
• Output PT00 Protection Fault Action (Parameter 304)
• Output PT00 Protection Fault Value (Parameter 305)
• Output PT01 Protection Fault Action (Parameter 310)
• Output PT01 Protection Fault Value (Parameter 311)
• Output PT02 Protection Fault Action (Parameter 316)
• Output PT02 Protection Fault Value (Parameter 317)
• Output Digital Module 1 Protection Fault Action (Parameter 322)
• Output Digital Module 1 Protection Fault Value (Parameter 323)
• Output Digital Module 2 Protection Fault Action (Parameter 328)
• Output Digital Module 2 Protection Fault Value (Parameter 329)
• Output Digital Module 3 Protection Fault Action (Parameter 334)
• Output Digital Module 3 Protection Fault Value (Parameter 335)
• Output Digital Module 4 Protection Fault Action (Parameter 340)
• Output Digital Module 4 Protection Fault Value (Parameter 342)
Default Value
1.0
Minimum Value
0.1
Maximum Value
25.0
Parameter Type
USINT
Size (Bytes)
1
Scaling Factor
10
Units
Sec