L3 Line Loss Trip Delay

L3 Line Loss Trip Delay (Parameter 288) allows the installer to define the time
period a L3 Line Loss condition must be present before a trip occurs. It is
adjustable from 0.1…25.0 seconds.

Table 116 - L3 Line Loss Trip Delay (Parameter 288)

L3 Line Loss Warning

The E300 Electronic Overload Relay will indicate an L3 Line Loss warning if:

No warning currently exists

IMPORTANT

The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:

Output PT00 Protection Fault Action (Parameter 304)

Output PT00 Protection Fault Value (Parameter 305)

Output PT01 Protection Fault Action (Parameter 310)

Output PT01 Protection Fault Value (Parameter 311)

Output PT02 Protection Fault Action (Parameter 316)

Output PT02 Protection Fault Value (Parameter 317)

Output Digital Module 1 Protection Fault Action (Parameter 322)

Output Digital Module 1 Protection Fault Value (Parameter 323)

Output Digital Module 2 Protection Fault Action (Parameter 328)

Output Digital Module 2 Protection Fault Value (Parameter 329)

Output Digital Module 3 Protection Fault Action (Parameter 334)

Output Digital Module 3 Protection Fault Value (Parameter 335)

Output Digital Module 4 Protection Fault Action (Parameter 340)

Output Digital Module 4 Protection Fault Value (Parameter 342)

Default Value

1.0

Minimum Value

0.1

Maximum Value

25.0

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

10

Units

Sec

IMPORTANT

The Line Loss Inhibit Timer starts when L1, L2, or L3 Line Loss protection is
activated by a programmed digital input (see Input Assignment Parameters
196-201). The E300 Electronic Overload Relay does not begin monitoring for
Line Loss condition until the Line Loss Inhibit Timer expires.