Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 59
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
59
System Operation and Configuration Chapter 3
Digital I/O Expansion Module 2 Type (Parameter 226)
The E300 Electronic Overload Relay supports up to four additional Digital I/O
expansion modules. This parameter configures the Option Match feature for the
Digital I/O expansion module at Digital Module Address 2. There are three
different types of Digital I/O expansion modules. Place the value of the expected
Digital I/O expansion module at Digital Module Address 2 into Parameter 226.
A value of (0) disables the Option Match feature for this Digital I/O expansion
module. A value of (1),
“No Digital I/O Expansion Module at Digital Module
Address 2”, makes the Digital I/O expansion module at Digital Module Address 2
not available to the Expansion Bus and prevents a user from connecting a Digital
I/O expansion module at Digital Module Address 2 to the E300 Electronic
Overload Relay system.
Table 30 - Digital I/O Expansion Module 2 Type (Parameter 226)
Digital I/O Expansion Module 3 Type (Parameter 227)
The E300 Electronic Overload Relay supports up to four additional Digital I/O
expansion modules. This parameter configures the Option Match feature for the
Digital I/O expansion module at Digital Module Address 3. There are three
different types of Digital I/O expansion modules. Place the value of the expected
Digital I/O expansion module at Digital Module Address 3 into Parameter 227.
A value of (0) disables the Option Match feature for this Digital I/O expansion
module. A value of (1),
“No Digital I/O Expansion Module at Digital Module
Address 3”, makes the Digital I/O expansion module at Digital Module Address 3
not available to the Expansion Bus and prevents a user from connecting a Digital
I/O expansion module at Digital Module Address 3 to the E300 Electronic
Overload Relay system.
Table 31 - Digital I/O Expansion Module 3 Type (Parameter 227)
Code
Description
Digital I/O Expansion Module Cat. No.
0
Ignore
—
1
No Digital I/O Expansion Module (Digital I/O Expansion
Module Not Available)
—
2
4 Inputs, 24V DC / 2 Relay Outputs
193-EXP-DIO-42-24D
3
4 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs
193-EXP-DIO-42-120
4
4 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs
193-EXP-DIO-42-240
Code
Description
Digital I/O Expansion Module Cat. No.
0
Ignore
—
1
No Digital I/O Expansion Module (Digital I/O Expansion
Module Not Available)
—
2
4 Inputs, 24V DC / 2 Relay Outputs
193-EXP-DIO-42-24D
3
4 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs
193-EXP-DIO-42-120
4
4 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs
193-EXP-DIO-42-240