Security Policy

The E300 Electronic Overload Relay has a security policy that can be used to
prevent users with malicious intent to potentially damage a motor or piece of
equipment. By default, the user can only modify the security policy when the
E300 Electronic Overload Relay is in Administration Mode (see

page 51

to learn

how to enable Administration Mode).

Table 38 - Security Policy (Parameter 211) Bit Function Detail

Device Configuration Policy

The Device Configuration Policy allows users to send external message
instructions via a communications network to write values to configuration
parameters. When this policy is disabled, all external message instructions with
configuration data will return a communications error when the E300 Electronic
Overload Relay is in Operation Mode or Run Mode.

Device Reset Policy

The Device Reset Policy allows users to send external message instruction via a
communications network to perform a soft device reset when the E300
Electronic Overload Relay is in Operation Mode. When this policy is disabled,
all external reset message instructions will return a communications error when
the E300 Electronic Overload Relay is in Operation Mode or Run Mode.

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Function

X

Device Configuration Enable

X

Device Reset Enable

X

Firmware Update Enable

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

X

Security Policy Config Enable