Automation controller communications, I/o messaging, Automation controller communications i/o messaging – Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 295
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
295
EtherNet/IP Communications Chapter 8
4.
A confirmation window will appear. Press OK.
NOTE:
If the user attempts to edit a configuration parameter when a Class 1
EtherNet/IP connection exists between an EtherNet/IP scanner and the E300
Electronic Overload Relay EtherNet/IP Communication Module, a message
similar to the one shown below will appear when the Apply button is pressed.
Automation Controller
Communications
The E300 Electronic Overload Relay EtherNet/IP Communication Module
supports two types of EtherNet/IP messaging.
•
I/O Messaging - Used for deterministic EtherNet/IP communications
with ControlLogix™, CompactLogix™, SoftLogix™, and EtherNet/IP
scanners. Its primary use is to read and write I/O data for control purposes.
•
Explicit Messaging - Used for non-deterministic communications in which
the data is not critical for control. Logic explicit messages have a lower
priority compared to I/O messages and are used to read and write non-
critical data.
I/O Messaging
RSLogix 5000™ and Studio 5000™ software is used to configure I/O messaging
between an automation controller and the E300 Electronic Overload Relay
EtherNet/IP Communication Module on an EtherNet/IP network.
Shown below are two examples and the steps necessary to configure a Logix
controller for I/O messaging.
•
Logix Configuration with Add-On Profile
•
Logix Configuration with a Generic Profile