Chapter 5 Protective Trip and Warning Functions

Table 127 - Over Voltage Trip Level (Parameter 361)

Over Voltage Warning

The E300 Electronic Overload Relay will indicate an Over Voltage warning if:

No warning currently exists

Over Voltage Warning is enabled

Voltage is present

Over Voltage Inhibit Time has expired

The maximum phase voltage is equal to or greater than the Over Voltage
Warning Level

When the Over Voltage Warning conditions are satisfied, the:

TRIP/WARN LED will flash a yellow 1-long / 2-short blink pattern

Bit 1 in Voltage Warning Status (Parameter 11) will set to 1

Bit 1 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Warning Alarm will close

Over Voltage Warn Level

Over Voltage Warn Level (Parameter 362) allows the user to define the voltage at
which the E300 Electronic Overload Relay will indicate a warning. It is user-
adjustable from 0…6553.5 volts.

Table 128 - Over Voltage Warn Level (Parameter 362)

Default Value

500.0

Minimum Value

0.0

Maximum Value

6553.5

Parameter Type

UINT

Size (Bytes)

2

Scaling Factor

10

Units

Volts

IMPORTANT

The Over Voltage Inhibit Time starts after a phase voltage transitions from 0V
to 20V L-L. The E300 Electronic Overload Relay does not begin monitoring for
an over voltage condition until the Over Voltage Inhibit Time expires.

Default Value

490.0

Minimum Value

0.0

Maximum Value

6553.5

Parameter Type

UINT

Size (Bytes)

2

Scaling Factor

10

Units

Volts