beautypg.com

Rockwell Automation 592- E300 Overload Relay User Manual User Manual

Page 109

background image

Rockwell Automation Publication 193-UM015B-EN-P - June 2014

109

Protective Trip and Warning Functions Chapter 5

No trip currently exists

L1 Under Current Trip is enabled

Current is present

Under Current Inhibit Timer has expired

L1 Percent FLA (Parameter 47) is less than the L1 Under Current Trip
Level for a time period greater than the L1 Under Current Trip Delay.

If the E300 Electronic Overload Relay trips on a L1 Under Current, the:

TRIP/WARN LED status indicator will flash a red 8-short blink pattern

Bit 7 in Current Trip Status (Parameter 4) will set to 1

Bit 0 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Trip Relay will open

Any relay outputs configured as a Control Relay will open

Any relay outputs configured as a Trip Alarm will close

Any relay outputs configured as a Normal Relay will be placed in their
Protection Fault state (if so programmed)

L1 Under Current Trip Delay

L1 Under Current Trip Delay (Parameter 266) allows the installer to define the
time period an L1 Under Current condition must be present before a trip occurs.
It is adjustable from 0.1…25.0 seconds.

IMPORTANT

The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:

Output PT00 Protection Fault Action (Parameter 304)

Output PT00 Protection Fault Value (Parameter 305)

Output PT01 Protection Fault Action (Parameter 310)

Output PT01 Protection Fault Value (Parameter 311)

Output PT02 Protection Fault Action (Parameter 316)

Output PT02 Protection Fault Value (Parameter 317)

Output Digital Module 1 Protection Fault Action (Parameter 322)

Output Digital Module 1 Protection Fault Value (Parameter 323)

Output Digital Module 2 Protection Fault Action (Parameter 328)

Output Digital Module 2 Protection Fault Value (Parameter 329)

Output Digital Module 3 Protection Fault Action (Parameter 334)

Output Digital Module 3 Protection Fault Value (Parameter 335)

Output Digital Module 4 Protection Fault Action (Parameter 340)

Output Digital Module 4 Protection Fault Value (Parameter 342)

This manual is related to the following products: