EtherNet/IP Information Appendix C
Table 387 - Discrete Output Point Object Class Attributes
11 instances of the Discrete Output Point Object are supported.
Table 388 - Discrete Output Point Object Instances
All instances contains the following attributes.
Table 389 - Discrete Output Point Object Instance Attributes
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
UINT
1
2
Get
Max. Instance
UINT
11
Instance
Name
Description
1
OutputPt00
Control Module Output 0
2
OutputPt01
Control Module Output 1
3
OutputPt02
Control Module Output 2
4
OutDigMod1Pt00
Digital Expansion Module 1 Output 0
5
OutDigMod1Pt01
Digital Expansion Module 1 Output 1
6
OutDigMod2Pt00
Digital Expansion Module 2 Output 0
7
OutDigMod2Pt01
Digital Expansion Module 2 Output 1
8
OutDigMod3Pt00
Digital Expansion Module 3 Output 0
9
OutDigMod3Pt01
Digital Expansion Module 3 Output 1
10
OutDigMod4Pt00
Digital Expansion Module 4 Output 0
11
OutDigMod4Pt01
Digital Expansion Module 4 Output 1
Attribute ID Access Rule
Name
Data Type
Value
3
Get
Value
BOOL
0=OFF, 1=ON
5
Get/Set
Fault Action
BOOL
0=Fault Value attribute, 1=Hold Last
State
6
Get/Set
Fault Value
BOOL
0=OFF, 1=ON
7
Get/Set
Idle Action
BOOL
0=Fault Value attribute, 1=Hold Last
State
8
Get/Set
Idle Value
BOOL
0=OFF, 1=ON
113
Get/Set
Pr Fault Action
BOOL
0=Pr Fault Value attribute, 1=Ignore
114
Get/Set
Pr Fault Value
BOOL
0=OFF, 1=ON
115
Get/Set
Force Enable
BOOL
0=Disable, 1=Enable
116
Get/Set
Force Value
BOOL
0=OFF, 1=ON
117
Get/Set
Input Binding
STRUCT:
USINT
Array of USINT
Size of appendix I encoded path
Appendix I encoded path: NULL path
means attribute 3 drives the output.
Otherwise, this is a path to a bit in an
instance of the DeviceLogix Data Table.