Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 407
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
407
EtherNet/IP Information Appendix C
Table 422 - DPI Fault Object Class Attributes
Five instances of the DPI Fault Object are supported.
Table 423 - DPI Fault Object Instance Attributes
The following common services are implemented for the DPI Fault Object.
Table 424 - DPI Fault Object Common Services
Attribute ID
Access Rule
Name
Data Type Value
1
Get
Class Revision
UINT
1
2
Get
Number of Instances
UINT
8
3
Get/Set
Fault Cmd Write
USINT
0=NOP; 1=Clear Fault; 2=Clear Flt
Queue
4
Get
Fault Instance Read
UINT
The instance of the Fault Queue Entry
containing information about the
Fault that tripped the Device
5
Get
Fault Data list
Struct of:
Number of Parameter Instances UINT
The total number of parameters
instances stored when a fault occurs
Parameter Instances
UINT [x ]
An array of parameters instance
numbers
6
Get
Number of Recorded Faults
UINT
The number of Faults recorded in the
Fault Queue
Attribute ID Access Rule
Name
Data Type
Value
0
Get
Full / All Info
Struct of:
Fault Code
UINT
See Fault Table below
Fault Source
Struct of:
DPI Port Number
USINT
0
Device Object
Instance
USINT
0x2c
Fault Text
BYTE[16]
See Fault Table below
Fault Time Stamp
Struct of:
Timer Value
ULINT
Timer Descriptor WORD
Help Object
Instance
UINT
Fault Data
1
Get
Basic Info
Struct of:
Fault Code
UINT
See
Fault Source
Struct of:
DPI Port Number
USINT
0
Device Object
Instance
USINT
0x2C
Fault Time Stamp
Struct of:
Timer Value
ULINT
Timer Descriptor
WORD
3
Get
Help Text
STRING
See
Service Code
Implemented for:
Service Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
Yes
No
Set_Attribute_Single