Chapter 5 Protective Trip and Warning Functions

Table 75 - Ground Fault Trip Delay (Parameter 243)

Ground Fault Trip Level

Ground Fault Trip Level (Parameter 244) allows the user to define the ground
fault current in which the E300 Electronic Overload Relay will trip and is
adjustable from:

0.500…5.00 A (Internal)

0.020…5.00 A (External)

Table 76 - Ground Fault Trip Level (Parameter 244)

Ground Fault Warning

The E300 Electronic Overload Relay will indicate a ground fault warning if:

No warning currently exists

Ground Fault Warning is enabled

Current is present

Ground Fault Inhibit Time has expired

Ground Fault Trip Delay (Parameter 243)

Default Value

0.5

Minimum Value

0.0

Maximum Value

25.0

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

10

Units

Sec

Ground Fault Trip Level (Parameter 244)

Default Value

2.5

Minimum Value

0.5 (internal); 0.02 (external)

Maximum Value

5.00

Parameter Type

UINT

Size (Bytes)

2

Scaling Factor

100

Units

Amps

IMPORTANT

The ground fault inhibit timer starts after the maximum phase load current
transitions from 0 A to 30% of the device’s minimum FLA rating or the ground
fault current is greater than or equal to 50% of the device’s minimum ground
fault current rating. The E300 Electronic Overload Relay does not begin
monitoring for a ground fault condition until the Ground Fault Current Inhibit
Time expires.