Chapter 3 System Operation and Configuration
Configure one of the Ptxx Input Assignments (Parameters 196…201) to
Emergency Start and activate the corresponding digital input.
Table 52 - Emergency Start (Parameter 216) Input PTXX Assignment (Parameters 196…201)
The user can also use a network command to activate the Emergency Start
feature. For the EtherNet/IP communications module, the user would set the
Emergency Start bit to 1 in Output Assembly 144. See
for more information on EtherNet/IP
communications.
When the Emergency Start feature is active, the following actions occur in the
E300 Electronic Overload Relay:
•
Protection trips are ignored
•
Output relays configured as Trip Relays are put into closed state
•
Normal operation resumes with any Normal or Control Relay assigned
output relay
•
The Emergency Start Active bit is set to 1 in Device Status 0
(Parameter 20) bit 6
Table 53 - Emergency Start (Parameter 216) Bit Function Detail— Device Status 0 (Parameter 20)
Value
Assignment
Description
0
Normal
Function as a digital input
1
Trip Reset
Reset the E300 when it is in a tripped state
2
Remote Trip
Force a the E300 to go into a tripped state
3
Activate FLA2
Use the value in FLA2 Setting (Parameter 177) for the current based
protection algorithms
4
Force Snapshot
Force the E300 to update its Snapshot log
5
Emergency Start
Issue an Emergency Start command
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Function
X
Trip Present
X
Warning Present
X
Invalid Configuration
X
Current Present
X
GFCurrent Present
X
Voltage Present
X
Emergency Start Enabled
X
DeviceLogix Enabled
X
Feedback Timeout Enabled
X
Operator Station Present
X
Voltage Sensing Present
X
Intern Ground Fault Sensing Present
X
Extern Ground Fault Sensing Present
X
PTC Sensing
X
Ready
Reserved