Metering and Diagnostics Chapter 7

Table 246 - L1 Current (Parameter 43)

L2 Current

L2 Current (Parameter 44) reports the current in Amperes flowing through the
L2 and T2 power terminals of the E300 Electronic Overload Relay Sensing
Module.

Table 247 - L2 Current (Parameter 44)

L3 Current

L3 Current (Parameter 45) reports the current in Amperes flowing through the
L3 and T3 power terminals of the E300 Electronic Overload Relay Sensing
Module.

Table 248 - L3 Current (Parameter 45)

Average Current

Average Current (Parameter 46) reports the average current of the monitored
current. When single or three phase (Parameter 176) is set to three phase, average
current is calculated as follows:
Average Current = (L1 Current + L2 Current + L3 Current) / 3

Default Value

0.00

Minimum Value

0.00

Maximum Value

20000000.00

Parameter Type

DINT

Size (Bytes)

4

Scaling Factor

100

Units

Amps

Default Value

0.00

Minimum Value

0.00

Maximum Value

20000000.00

Parameter Type

DINT

Size (Bytes)

4

Scaling Factor

100

Units

Amps

Default Value

0.00

Minimum Value

0.00

Maximum Value

20000000.00

Parameter Type

DINT

Size (Bytes)

4

Scaling Factor

100

Units

Amps