Preventive Maintenance
The E300 Electronic Overload Relay offers preventive maintenance warnings
based on the number of start cycles and the number of operating hours. These
warnings can be used to alert the user that the number of starts or number of
operating hours has been reached, and it is time to perform preventive
maintenance.
Number of Starts Warning
The E300 Electronic Overload Relay will warn with a number of starts warning
indication if:
•
No warning currently exists
•
Number of Starts Warning is enabled
•
The value in Starts Counter (Parameter 29) is greater than the value set in
Total Starts (Parameter 207)
If the E300 Electronic Overload Relay warns on a number of starts warning, the
following will occur:
•
The TRIP/WARN LED will flash a red 3-long / 12-short blink pattern
•
Bit 11 in Control Warning Status (Parameter 13) will set to 1
•
Bit 1 in Device Status 0 (Parameter 20) will set to 1
•
Any relay outputs configured as a Warning Alarm will close
Total Starts
Total Starts (Parameter 207) allows the user to set the number starts until the
starts counter warning occurs.
Table 204 - Total Starts (Parameter 207)
Starts Counter
Starts Counter (Parameter 29) represents the number of times a motor has been
started. This value can be reset to zero using the Clear Command (Parameter
165) function
Clear Operating Statistics.
Default Value
0
Minimum Value
0
Maximum Value
65535
Parameter Type
UINT
Size (Bytes)
2
Scaling Factor
1
Units