284

Rockwell Automation Publication 193-UM015B-EN-P - June 2014

Chapter 8 EtherNet/IP Communications

The New Entry window appears with the module's Ethernet Address (MAC).

6.

Type the IP address, host name, and a module description.

7.

Click OK.

8.

Cycle power to the E300 Electronic Overload Relay EtherNet/IP
Communication Module.

9.

To permanently assign this configuration to the module: Select the
module in the Relation List panel and click Disable BOOTP/DHCP.

When module power is cycled, it uses the assigned configuration and does not
issue a DHCP request.

If you do not click Disable BOOTP/DHCP, on a power cycle, the module clears
the current IP configuration and will again begin sending DHCP requests.