System Operation and Configuration Chapter 3
Electronic Overload Relay system. Users can configure an option mismatch to
cause a protection trip or provide a warning within the E300.
Enable Option Match Protection Trip (Parameter 186)
To enable the E300 Electronic Overload Relay’s Option Match feature to cause a
protection trip in the event of an option mismatch, place a (1) in bit position 8 of
Parameter 186 (Control Trip Enable). Users can select the specific option match
features to cause a protection trip in Parameter 233 (Option Match Action).
Table 23 - Enable Option Match Protection Trip Bit Function Detail— Control Trip Enable
(Parameter 186)
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Function
X
Test Trip Enable
X
PTC Trip Enable
X
DeviceLogix Trip Enable
X
Operator Station Trip Enable
X
Remote Trip Enable
X
Blocked Start Trip Enable
X
Hardware Fault Trip Enable
X
Configuration Trip Enable
X
Option Match Trip Enable
X
Feedback Timeout Trip Enable
X
Expansion Bus Trip Enable
Reserved
Reserved
X
Non-Volatile Memory Trip Enable
X
Ready
Reserved