Chapter 6 Commands

Table 210 - Clear Command (Parameter 165)

Clear Operating Statistics

When the Clear Operating Statistics command is issued, the E300 Electronic
Overload Relay will set the following parameters to a value of zero (0):

Operating Time (Parameter 28)

Starts Counter (Parameter 29)

Clear History Logs

When the Clear History Logs command is issued, the E300 Electronic Overload
Relay will set the following parameters to a value of zero (0):

Trip History 0 (Parameter 127)

Trip History 1 (Parameter 128)

Trip History 2 (Parameter 129)

Trip History 3 (Parameter 130)

Trip History 4 (Parameter 131)

Warning History 0 (Parameter 132)

Warning History 1 (Parameter 133)

Warning History 2 (Parameter 134)

Warning History 3 (Parameter 135)

Warning History 4 (Parameter 136)

Default Value

0 = Ready

Range

0 = Ready

1 = Clear Operating Statistics

2 = Clear History Logs

3 = Clear %TCU

4 = Clear kWh

5 = Clear kVARh

6 = Clear kVAh

7 = Clear Max kW Demand

8 = Clear Max kVAR Demand

9 = Clear Max kVA Demand

10 = Clear All

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

1

Units