System Operation and Configuration Chapter 3

Input Pt05 Assignment (Parameter 201)

Input Pt05 Assignment (Parameter 201) allows the user to assign this digital
input for the following functions:

Table 44 - Input Pt05 Assignment (Parameter 201)

Value

Assignment

Description

0

Normal

Function as a digital input

1

Trip Reset

Reset the E300 when it is in a tripped state

2

Remote Trip

Force a the E300 to go into a tripped state

3

Activate FLA2

Use the value in FLA2 Setting (Parameter 177) for the current based protection
algorithms

4

Force Snapshot

Force the E300 to update its Snapshot log

5

Emergency Start

Issue an Emergency Start command

6

Test Mode

Enable Test Mode monitoring

7

L1 Line Loss Arm

Activate L1 Line Loss Protection

8

L2 Line Loss Arm

Activate L2 Line Loss Protection

9

L3 Line Loss Arm

Activate L3 Line Loss Protection

10

L1 L2 Line Loss Arm

Activate L1 and L2 Line Loss Protection

11

L2 L3 Line Loss Arm

Activate L2 and L3 Line Loss Protection

12

L1 L3 Line Loss Arm

Activate L1 and L3 Line Loss Protection

13

L1 L2 L3 Line Loss Arm

Activate L1, L2, and L3 Line Loss Protection