Rockwell Automation Publication 193-UM015B-EN-P - June 2014

Chapter 7 Metering and Diagnostics

When single or three phase (Parameter 176) is set to single phase, average current
is calculated as follows:
Average Current = (L1 Current + L2 Current) / 2

Table 249 - Average Current (Parameter 46)

L1 Percent FLA

L1 Percent FLA (Parameter 47) reports the L1 current in comparison to the
active Full Load Amps programmed in FLA (Parameter 171) and FLA2
(Parameter 177).
L1 Percent FLA = L1 Current / Full Load Amps

Table 250 - L1 Percent FLA (Parameter 47)

L2 Percent FLA

L2 Percent FLA (Parameter 48) reports the L2 current in comparison to the
active Full Load Amps programmed in FLA (Parameter 171) and FLA2
(Parameter 177).
L2 Percent FLA = L2 Current / Full Load Amps

Table 251 - L2 Percent FLA (Parameter 48)

Default Value

0.00

Minimum Value

0.00

Maximum Value

20000000.00

Parameter Type

DINT

Size (Bytes)

4

Scaling Factor

100

Units

Amps

Default Value

0.0

Minimum Value

0.0

Maximum Value

1000.00

Parameter Type

UINT

Size (Bytes)

2

Scaling Factor

10

Units

%

Default Value

0.0

Minimum Value

0.0

Maximum Value

1000.00

Parameter Type

UINT

Size (Bytes)

2

Scaling Factor

10

Units

%

This manual is related to the following products: