L1 percent fla, L2 percent fla, L1 percent fla l2 percent fla – Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 240
![background image](/manuals/577641/240/background.png)
240
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Chapter 7 Metering and Diagnostics
When single or three phase (Parameter 176) is set to single phase, average current
is calculated as follows:
Average Current = (L1 Current + L2 Current) / 2
Table 249 - Average Current (Parameter 46)
L1 Percent FLA
L1 Percent FLA (Parameter 47) reports the L1 current in comparison to the
active Full Load Amps programmed in FLA (Parameter 171) and FLA2
(Parameter 177).
L1 Percent FLA = L1 Current / Full Load Amps
Table 250 - L1 Percent FLA (Parameter 47)
L2 Percent FLA
L2 Percent FLA (Parameter 48) reports the L2 current in comparison to the
active Full Load Amps programmed in FLA (Parameter 171) and FLA2
(Parameter 177).
L2 Percent FLA = L2 Current / Full Load Amps
Table 251 - L2 Percent FLA (Parameter 48)
Default Value
0.00
Minimum Value
0.00
Maximum Value
20000000.00
Parameter Type
DINT
Size (Bytes)
4
Scaling Factor
100
Units
Amps
Default Value
0.0
Minimum Value
0.0
Maximum Value
1000.00
Parameter Type
UINT
Size (Bytes)
2
Scaling Factor
10
Units
%
Default Value
0.0
Minimum Value
0.0
Maximum Value
1000.00
Parameter Type
UINT
Size (Bytes)
2
Scaling Factor
10
Units
%