Table 429 – Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 411
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
411
EtherNet/IP Information Appendix C
The following common services are implemented for the DPI Warning Object.
Table 428 - DPI Warning Object Common Services
The table below lists Warning Codes, Warning Text, and Warning Help Strings.
Table 429 - Warning Codes, Warning Text, and Warning Help Strings
Service Code
Implemented for:
Service Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
Yes
No
Set_Attribute_Single
Warning
Code
Warning Text
Warning Help Text
0
No Warning
No Warning Conditions Detected
1
OverloadWarning
Approaching a motor current overload condition
2
Warning2
3
Ground Fault
Power conductor or motor winding is shorting to ground
4
Warning4
5
JamWarning
Motor current has exceed the programmed jam warning level
6
UnderloadWarning
Motor current has fallen below normal operating levels
7
Current ImbalWarn
Phase to phase current imbalance detected
8
L1UnderCurrWarn
L1Current was below L1 Undercurrent Warning Level
9
L2UnderCurrWarn
L2Current was below L2 Undercurrent Warning Level
10
L3UnderCurrWarn
L3Current was below L3 Undercurrent Warning Level
11
L1OverCurrenWarn
L1 Current was over L1 Overcurrent Warning Level
12
L2OverCurrenWarn
L2 Current was over L2 Overcurrent Warning Level
13
L3OverCurrenWarn
L3 Current was over L3 Overcurrent Warning Level
14
L1LineLossWarn
L1 Current Lost for longer than the L1 Loss Trip Delay
15
L2LineLossWarn
L2 Current Lost for longer than the L2 Loss Trip Delay
16
L3LineLossWarn
L3 Current Lost for longer than the L3 Loss Trip Delay
17
UnderVoltageWarn
Line to Line Under-Voltage condition detected
18
OvervoltageWarn
Line to Line Over-Voltage condition detected
19
VoltageUnbalWarn
Phase to phase voltage imbalance detected
20
PhaseRotationWrn
The unit detects the supply voltage phases are rotated
21
UnderFreqWarning
Line voltage frequency is below the warning level
22
OverFreqWarning
Line voltage frequency has exceeded warning level
23
Warning23
24
Warning24
25
Warning25
26
Warning26
27
Warning27
28
Warning28
29
Warning29
30
Warning30
31
Warning31
32
Warning32
33
UnderKWWarning
Total Real Power (kW) is below warning level
34
OverKWWarning
Total Real Power (kW) has exceeded warning level
35
UnderKVARConWarn
Under Reactive Power Consumed (+kVAR) condition detected
36
OverKVARConWarn
Over Reactive Power Consumed (+kVAR) condition detected
37
UnderKVARGenWarn
Under Reactive Power Generated (-kVAR) condition detected