Rockwell Automation Publication 193-UM015B-EN-P - June 2014

Chapter 3 System Operation and Configuration

Analog I/O Expansion Module 4 Type (Parameter 232)

The E300 Electronic Overload Relay supports up to four additional Analog I/O
expansion modules. This parameter configures the Option Match feature for the
Analog I/O expansion module at Analog Module Address 4. There are three
different types of Analog I/O expansion modules. Place the value of the expected
Analog I/O expansion module at Analog Module Address 4 into Parameter 232.
A value of (0) disables the Option Match feature for this Analog I/O expansion
module. A value of (1),

“No Analog I/O Expansion Module at Analog Module

Address 4”, makes the Analog I/O expansion module at Analog Module Address 4
not available to the Expansion Bus and prevents a user from connecting a Analog
I/O expansion module at Analog Module Address 4 to the E300 Electronic
Overload Relay system.

Table 36 - Analog I/O Expansion Module 4 Type (Parameter 232)

Option Match Action (Parameter 233)

The Option Match feature for the E300 Electronic Overload Relay allows the
user to specify an action when there is an option mismatch – Protection Trip or
Warning. Place a (0) in the appropriate bit position for a warning, and place a
(1) in the appropriate bit position to cause a protection trip if there is an option
mismatch.

Table 37 - Option Match Action (Parameter 233) Bit Function Detail

Code

Description

Analog I/O Expansion Module Cat. No.

0

Ignore

1

No Analog I/O Expansion Module (Analog I/O Expansion
Module Not Available)

2

3 Universal Analog Inputs / 1 Analog Output

193-EXP-AIO-31

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Function

X

Control Module Mismatch Action

X

Sensing Module Mismatch Action

X

Communication Module Mismatch
Action

X

Operator Station Mismatch Action

X

Digital Module 1 Mismatch Action

X

Digital Module 2 Mismatch Action

X

Digital Module 3 Mismatch Action

X

Digital Module 4 Mismatch Action

X

Analog Module 1 Mismatch Action

X

Analog Module 2 Mismatch Action

X

Analog Module 3 Mismatch Action

X

Analog Module 4 Mismatch Action

This manual is related to the following products: