System Operation and Configuration Chapter 3
Output Pt02 Assignment (Parameter 204)
Output Pt02 Assignment (Parameter 204) allows the user to assign this relay
output for the following functions:
Table 47 - Output Pt02 Assignment (Parameter 204)
Activate FLA2 with Output Relay (Parameter 209)
Activate FLA2 with Output Relay (Parameter 209) allows a user to activate the
value in FLA2 Setting (Parameter 177) for the current based protection
algorithms when the assigned output relay is in an energized state.
Table 48 - Activate FLA2 with Output Relay (Parameter 209)
Expansion Bus Fault
The E300 Electronic Overload Relay’s expansion bus can be used to expand the
I/O capabilities of the E300 Electronic Overload Relay with the addition of
digital and analog expansion I/O modules. The Expansion Bus Fault allows a user
to have the E300 Electronic Overload Relay go into a Trip or Warning state when
established Expansion Bus communications is disrupted between the Control
Module and any digital and analog expansion I/O modules.
The Expansion Bus Fault is used when the Option Match feature is not enabled
for the digital and/or analog expansion I/O modules. The Expansion Bus Fault
only monitors for communication disruptions between the Control Module and
digital and/or analog expansion I/O modules. Expansion bus communication
disruptions between the Control Module and Operator Station do not affect the
Expansion Bus fault.
Value
Assignment
Description
0
Normal
Function as a relay output
1
Trip Relay
Function as a normally closed contact until the E300 is in a tripped state in which the relay
opens. The Trip Relay remains open until a trip reset is issued.
2
Control Relay
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open
state until the relay is commanded to close by communications or via a DeviceLogix
program. When the E300 enters into a tripped state the Control Relay opens and remains
open until a trip reset is issued.
3
Trip Alarm
Function as a normally open contact until the E300 is in a tripped state in which the relay
closes. The Trip Alarm remains closed until a trip reset is issued.
4
Warning Alarm
Function as a normally open contact until the E300 is in a protection warning state in which
the relay closes. The Warning Alarm remains closed until the protection warning clears.
Value
Description
0
Disable
1
Pt00 Output
2
Pt01 Output
3
Pt02 Output