System Operation and Configuration Chapter 3

Output Pt02 Assignment (Parameter 204)

Output Pt02 Assignment (Parameter 204) allows the user to assign this relay
output for the following functions:

Table 47 - Output Pt02 Assignment (Parameter 204)

Activate FLA2 with Output Relay (Parameter 209)

Activate FLA2 with Output Relay (Parameter 209) allows a user to activate the
value in FLA2 Setting (Parameter 177) for the current based protection
algorithms when the assigned output relay is in an energized state.

Table 48 - Activate FLA2 with Output Relay (Parameter 209)

Expansion Bus Fault

The E300 Electronic Overload Relay’s expansion bus can be used to expand the
I/O capabilities of the E300 Electronic Overload Relay with the addition of
digital and analog expansion I/O modules. The Expansion Bus Fault allows a user
to have the E300 Electronic Overload Relay go into a Trip or Warning state when
established Expansion Bus communications is disrupted between the Control
Module and any digital and analog expansion I/O modules.

The Expansion Bus Fault is used when the Option Match feature is not enabled
for the digital and/or analog expansion I/O modules. The Expansion Bus Fault
only monitors for communication disruptions between the Control Module and
digital and/or analog expansion I/O modules. Expansion bus communication
disruptions between the Control Module and Operator Station do not affect the
Expansion Bus fault.

Value

Assignment

Description

0

Normal

Function as a relay output

1

Trip Relay

Function as a normally closed contact until the E300 is in a tripped state in which the relay
opens. The Trip Relay remains open until a trip reset is issued.

2

Control Relay

Function as a combination Normal and Trip Relay. The Control Relay is in a normally open
state until the relay is commanded to close by communications or via a DeviceLogix
program. When the E300 enters into a tripped state the Control Relay opens and remains
open until a trip reset is issued.

3

Trip Alarm

Function as a normally open contact until the E300 is in a tripped state in which the relay
closes. The Trip Alarm remains closed until a trip reset is issued.

4

Warning Alarm

Function as a normally open contact until the E300 is in a protection warning state in which
the relay closes. The Warning Alarm remains closed until the protection warning clears.

Value

Description

0

Disable

1

Pt00 Output

2

Pt01 Output

3

Pt02 Output