Protective Trip and Warning Functions Chapter 5

Table 86 - Underload Trip Delay (Parameter 256)

Underload Trip Level

Underload Trip Level (Parameter 257) allows the installer to define the current at
which the E300 Electronic Overload Relay will trip on an underload. It is user-
adjustable from 10…100% of the FLA Setting (Parameter 171).

Table 87 - Underload Trip Level (Parameter 257)

Underload Warning

The E300 Electronic Overload Relay will indicate an underload warning if:

No warning currently exists

Underload Warning is enabled

Current is present

Underload Inhibit Time has expired

The minimum phase current is less than the Underload Warning Level

When the Underload Warning conditions are satisfied, the:

Default Value

5.0

Minimum Value

0.1

Maximum Value

25.0

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

10

Units

Sec

Default Value

50

Minimum Value

10

Maximum Value

100

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

1

Units

%FLA

IMPORTANT

The Underload Inhibit Timer starts after the maximum phase of load current
transitions from 0 A to 30% of the device’s minimum FLA setting. The E300
Electronic Overload Relay does not begin monitoring for an underload
condition until the Underload Inhibit Time expires.

IMPORTANT

For any given application, the practical limit of the Underload Trip Level
(Parameter 246), will be dependent on the FLA Setting and the lower limit of
the E300 Electronic Overload Relay’s current measurement capability.