Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 343

Rockwell Automation Publication 193-UM015B-EN-P - November 2013
343
Parameter List Appendix B
Trip/Warn History
(continued)
149
WarnHistoryMaskA
Warning History Mask for Analog
Input Based Warnings
UINT
2
1
Bit0= InAnMod1Ch00Warn
Bit1= InAnMod1Ch01Warn
Bit2= InAnMod1Ch02Warn
Bit3= InAnMod2Ch00Warn
Bit4= InAnMod2Ch01Warn
Bit5= InAnMod2Ch02Warn
Bit6= InAnMod3Ch00Warn
Bit7= InAnMod3Ch01Warn
Bit8= InAnMod3Ch02Warn
Bit9= InAnMod4Ch00Warn
Bit10= InAnMod4Ch01Warn
Bit11= InAnMod4Ch02Warn
0xFFF
150
Reserved
Trip Snapshot
151
TSL1Current
Snapshot of the actual L1 Phase
Current at trip
DINT
4
100
0
2000000000 0
Amps
152
TSL2Current
Snapshot of the actual L2 Phase
Current at trip
DINT
4
100
0
2000000000 0
Amps
153
TSL3Current
Snapshot of the actual L3 Phase
Current at trip
DINT
4
100
0
2000000000 0
Amps
154
TSThermUtilized
Snapshot of % Thermal Capacity
Used at trip
UINT
2
1
0
100
0
%
155
TSGFCurrent
Snapshot of the Ground Fault
Current at trip
INT
2
100
0
2540
0
Amps
156
TSL1toL2Voltage
Snapshot of 3 Phase RMS Voltage
Line-Line at trip
UINT
2
10
0
65535
0
Volt
157
TSL2toL3Voltage
Snapshot of 3 Phase RMS Voltage
Line-Line at trip
UINT
2
10
0
65535
0
Volt
158
TSL3toL1Voltage
Snapshot of 3 Phase RMS Voltage
Line-Line at trip
UINT
2
10
0
65535
0
Volt
159
TSTotalRealPwr
Snapshot of Total Real Power at
trip
DINT
4
1000
-2000000000 2000000000 0
kW
160
TSTotalkVAR
Snapshot of Total Reactive Power
at trip
DINT
4
1000
-2000000000 2000000000 0
kVAR
161
TSTotalkVA
Snapshot of Total Apparent
Power at trip
DINT
4
1000
0
2000000000 0
kVA
162
TSTotalPF
Snapshot of Total True Power
Factor (PF) at trip
INT
2
10
-1000
1000
0
%
Command
163
TripReset
Attempt to reset a trip
BOOL
0=Ready
1=TripReset
0
1
0
164
ConfigPreset
IO Configuration based on Logic
Personality
USINT
0=Ready
1=Factory Defaults
0
54
0
165
ClearCommand
Reset Accumulator(s)
USINT
1
1
0= Ready
1= ClrOperStats
2= ClrHistoryLogs
3= ClrPercentTCU
4= ClrKWh
5= ClrKVARh
6= ClrKVAh
7= ClrMaxKWDemad
8= ClrMaxKVARDemand
9= ClrMaxKVADemand
10= ClearAll
0
166
Reserved
167
Reserved
168
Reserved
Group
Param
No.
Parameter Name
Description
Type
Data Size
(bytes)
Scale
Factor
Min
Max
Default Units