Protective Trip and Warning Functions Chapter 5

Over kVA Trip Delay

Over kVA Trip Delay (Parameter 407) allows the installer to define the time
period an over apparent power (kVA) condition must be present before a trip
occurs. It is adjustable from 0.1…25.0 seconds.

Table 177 - Over kVA Trip Delay (Parameter 407)

Over kVA Trip Level

Over kVA Trip Level (Parameter 408) allows the installer to define the total
apparent power (kVA) at which the E300 Electronic Overload Relay will trip on
over apparent power (kVA). It is user-adjustable from 0…2,000,000 kVA.

IMPORTANT

The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:

Output PT00 Protection Fault Action (Parameter 304)

Output PT00 Protection Fault Value (Parameter 305)

Output PT01 Protection Fault Action (Parameter 310)

Output PT01 Protection Fault Value (Parameter 311)

Output PT02 Protection Fault Action (Parameter 316)

Output PT02 Protection Fault Value (Parameter 317)

Output Digital Module 1 Protection Fault Action (Parameter 322)

Output Digital Module 1 Protection Fault Value (Parameter 323)

Output Digital Module 2 Protection Fault Action (Parameter 328)

Output Digital Module 2 Protection Fault Value (Parameter 329)

Output Digital Module 3 Protection Fault Action (Parameter 334)

Output Digital Module 3 Protection Fault Value (Parameter 335)

Output Digital Module 4 Protection Fault Action (Parameter 340)

Output Digital Module 4 Protection Fault Value (Parameter 342)

Default Value

1.0

Minimum Value

0.1

Maximum Value

25.0

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

10

Units

Sec