Appendix B Parameter List
Trip/Warn History
(continued)
145
WarnHistoryMaskI
Warning History Mask for Current
Based Warnings
UINT
2
1
Bit0= OverloadWarning
Bit1= Reserved
Bit2= GroundFltWarning
Bit3= Reserved
Bit4= JamWarning
Bit5= UnderloadWarning
Bit6= CurrentImbalWarn
Bit7= L1UnderCurrWarn
Bit8= L2UnderCurrWarn
Bit9= L3UnderCurrWarn
Bit10= L1OverCurrenWarn
Bit11= L2OverCurrenWarn
Bit12= L3OverCurrenWarn
Bit13= L1LineLossWarn
Bit14= L2LineLossWarn
Bit15= L3LineLossWarn
0xFFFF
146
WarnHistoryMaskV
Warning History Mask for Voltage
Based Warnings
UINT
2
1
Bit0= UnderVoltageWarn
Bit1= OvervoltageWarn
Bit2= VoltageUnbalWarn
Bit3= PhaseRotationWrn
Bit4= UnderFreqWarning
Bit5= OverFreqWarning
0x3F
147
WarnHistoryMaskP
Warning History Mask for Power
Based Warnings
UINT
2
1
Bit0= UnderKWWarning
Bit1= OverKWWarning
Bit2= UnderKVARConWarn
Bit3= OverKVARConWarn
Bit4= UnderKVARGenWarn
Bit5= OverKVARGenWarn
Bit6= UnderKVAWarning
Bit7= OverKVAWarning
Bit8= UnderPFLagWarn
Bit9= OverPFLagWarn
Bit10= UnderPFLeadWarn
Bit11= OverPFLeadWarn
0xFFF
148
WarnHistoryMaskC
Warning History Mask for Control
Based Warnings
UINT
2
1
Bit0= Reserved
Bit1= PTCWarning
Bit2= DLXWarning
Bit3= Reserved
Bit4= Reserved
Bit5= Reserved
Bit6= Reserved
Bit7= ConfigWarning
Bit8= OptionMatchWarn
Bit9= DLXFBTimeoutWarn
Bit10= ExpansionBusWarn
Bit11= PMNumberOfStarts
Bit12= PMOperatingHours
0x1FFF
Group
Param
No.
Parameter Name
Description
Type
Data Size
(bytes)
Scale
Factor
Min
Max
Default Units