342

Rockwell Automation Publication 193-UM015B-EN-P - November 2013

Appendix B Parameter List

Trip/Warn History

(continued)

145

WarnHistoryMaskI

Warning History Mask for Current
Based Warnings

UINT

2

1

Bit0= OverloadWarning
Bit1= Reserved
Bit2= GroundFltWarning
Bit3= Reserved
Bit4= JamWarning
Bit5= UnderloadWarning
Bit6= CurrentImbalWarn
Bit7= L1UnderCurrWarn
Bit8= L2UnderCurrWarn
Bit9= L3UnderCurrWarn
Bit10= L1OverCurrenWarn
Bit11= L2OverCurrenWarn
Bit12= L3OverCurrenWarn
Bit13= L1LineLossWarn
Bit14= L2LineLossWarn
Bit15= L3LineLossWarn

0xFFFF

146

WarnHistoryMaskV

Warning History Mask for Voltage
Based Warnings

UINT

2

1

Bit0= UnderVoltageWarn
Bit1= OvervoltageWarn
Bit2= VoltageUnbalWarn
Bit3= PhaseRotationWrn
Bit4= UnderFreqWarning
Bit5= OverFreqWarning

0x3F

147

WarnHistoryMaskP

Warning History Mask for Power
Based Warnings

UINT

2

1

Bit0= UnderKWWarning
Bit1= OverKWWarning
Bit2= UnderKVARConWarn
Bit3= OverKVARConWarn
Bit4= UnderKVARGenWarn
Bit5= OverKVARGenWarn
Bit6= UnderKVAWarning
Bit7= OverKVAWarning
Bit8= UnderPFLagWarn
Bit9= OverPFLagWarn
Bit10= UnderPFLeadWarn
Bit11= OverPFLeadWarn

0xFFF

148

WarnHistoryMaskC

Warning History Mask for Control
Based Warnings

UINT

2

1

Bit0= Reserved
Bit1= PTCWarning
Bit2= DLXWarning
Bit3= Reserved
Bit4= Reserved
Bit5= Reserved
Bit6= Reserved
Bit7= ConfigWarning
Bit8= OptionMatchWarn
Bit9= DLXFBTimeoutWarn
Bit10= ExpansionBusWarn
Bit11= PMNumberOfStarts
Bit12= PMOperatingHours

0x1FFF

Group

Param

No.

Parameter Name

Description

Type

Data Size

(bytes)

Scale

Factor

Min

Max

Default Units