Chapter 5 Protective Trip and Warning Functions

L3 Over Current Trip Delay

L3 Over Current Trip Delay (Parameter 282) allows the installer to define the
time period a L3 Over Current condition must be present before a trip occurs. It
is adjustable from 0.1…25.0 seconds.

Table 110 - L3 Over Current Trip Delay (Parameter 282)

L3 Over Current Trip Level

L3 Over Current Trip Level (Parameter 283) allows the installer to define the
current at which the E300 Electronic Overload Relay will trip on a L3 Over
Current. It is user-adjustable from 10…100% of the FLA Setting (Parameter
171).

Table 111 - L3 Over Current Trip Level (Parameter 283)

L3 Over Current Warning

The E300 Electronic Overload Relay will indicate an L3 Over Current warning
if:

No warning currently exists

L3 Over Current Warning is enabled

Current is present

The Over Current Inhibit Timer has expired

Default Value

1.0

Minimum Value

0.1

Maximum Value

25.0

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

10

Units

Sec

Default Value

100

Minimum Value

10

Maximum Value

100

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

1

Units

%FLA

IMPORTANT

The Over Current Inhibit Timer starts after the maximum phase of load current
transitions from 0A to 30% of the device’s minimum FLA setting. The E300
Electronic Overload Relay does not begin monitoring for an over current
condition until the Over Current Inhibit Time expires.