Westermo OS Management Guide
Version 4.17.0-0
24.3.2.3
Power Trigger Configuration Example
Syntax trigger power
Context
context
Usage Create a power trigger, and enter the
context
for this trigger.
Additional settings for power triggers are listed below. The only mandatory
setting is the list of power sensors - no power alarm events will occur until
power sensors are defined.
❼ Sensor: WeOS units typically have two power sensors; sensor 1 for DC1
and sensor 2 for DC2. Use ”show env” (in Admin Exec context) to list
available sensors, see
❼ Enable/Disable: By default, the trigger is enabled.
❼ Severity: By default, active severity is WARNING and inactive severity
is NOTIFY.
❼ Action: By default, the trigger is mapped to the default action profile
(action 1).
Example
example:/#> configure
example:/config/#> alarm
example:/config/alarm/#> trigger power
Created trigger 1
example:/config/alarm/trigger-1/#> sensor 1,2
example:/config/alarm/trigger-2/#> end
example:/config/alarm/#> show
Trigger
Type
Enabled
Action
Source
==============================================
1
power
YES
1
1 2
Action
Targets
===============================================================================
1
snmp log led digout
===============================================================================
Summary alarm traps: Disabled
example:/config/alarm/#>